Industrial Thermistor Temperature Sensors (RTDs)
Teltru - NPAA3
Tel-Tru's thermistor (RTD) sensors are designed for the most demanding industrial applications. RTD thermometers...
Technical Description
Easy to install
High accuracy, long-term stability, consistent repeatability.
Fast response time
Options include a wide selection of connectors.
It has a calibration certificate according to NIST standards.
Applications
There are various configurations to meet the requirements of many markets, including Chemical Processing, Oil & Gas, Construction, Cold Storage, Water/Wastewater, HVAC, and Original Equipment Manufacturers (OEMs).
Specifications
- Protection Class: IP67 (NEMA 6)
- Operating Temperature: -40°C to 80°C
- Probe Length: 2.5" to 12" (6.35cm to 30.48cm)
- Probe Diameter: 0.187" or 0.250" (0.47cm to 0.64cm)
- Probe and Housing Material: 316SS Stainless Steel with Threaded Connector
- Maximum Operating Pressure: 1500 PSIG (probe only)
- Input: RTD, Pt100 type (α=0.00385), 3-wire
- Accuracy: Class A +/- 0.06% at 0°C - Complies with IEC 751
- Conductors: 3-wire, Teflon Insulation
- Connectors: Options include no connector (bare wire), M12 connector
- Output (with transmitter): 4 to 20mA or HART
- Temperature range: See order information.
| Standard temperature range | |
| E | Range°C |
| 01 | -50/260°C |
| Temperature range of the Hart communication transmitter type | |
| E | Range°C |
| 71 | -50/100 |
| 72 | -50/25 |
| 73 | -50/50 |
| 84 | -40/70 |
| 86 | -20/120 |
| 74 | -10/110 |
| 75 | 0/50 |
| 95 | 0/60 |
| EI | 0/80 |
| 76 | 0/100 |
| 77 | 0/150 |
| 78 | 0/200 |